Field display isolated temperature transmitter
CZWB230-G  Field display isolated temperature transmitter
LCD backlight display; Input and output are each galvanically isolated;signal type and range can be configured through computer;Temperature drift:0.01%FS/℃
Number of channels:
1input 1output
Input signal:
Pt100;Cu50;Cu100;T;E;J;K;N;R;S;B
Output Signal:
4~20mA(Without Energy)
Supply Voltage:
Loop Power Suply
CZWB230-G
产品详情
产品参数
下载
click to consult
加入对比
加入询价单


Field display isolated temperature transmitter


Product Name  CZWB230-G Temperature Transmitter
Number of channels  1
Supply voltage(Ue)  16~28V DC
Input signal  Pt100;Cu50;Cu100;T;E;J;K;N;R;S;B;mV
Output current  4~20mA
Weight  Approx 950g

Field display isolated temperature transmitter

Field display isolated temperature transmitter

Field display isolated temperature transmitter


Field display isolated temperature transmitter


Product characteristic
General
Input data
Output data
Power supply
Housing
EMC data
Operating conditions
Connection data
Others
Function
产品参数
Product characteristic
Characteristic LED Display
General
Number of channels 1
Dielectric strength 1500V AC;1minute(between input and output )
Temperature drift 0.01%FS/℃
Response time Reach 90% of final value in 5s
Insulation resistance ≥100MΩ;500V DC(between input and output)
Electromagnetic compatibility According to IEC 61326-1(GB/T 18268)
Weight Approx 950g
Input data
Input signal Pt100;Cu50;Cu100;T;E;J;K;N;R;S;B;mV
Output data
Output current 4~20mA
Current output load resistance RL≤(Ue-16)/0.021Ω
Alarm indication Lower limit overflow alarm,output current ≈3.8mA;Upper limit overflow and breakage alarm,output current ≈20.8mA
Power supply
Supply voltage(Ue) 16~28V DC
Power supply mode Loop powered
Housing
Material AL
Colour white
EMC data
Electrical fast transient/burst immunity According to:IEC 61326-1
Surge immunity According to:IEC 61326-1
Radiated,radio-frequency,electromagnetic field immunity According to:IEC 61326-1
Electrostatic discharge immunity According to:IEC 61326-1
Immunity to conducted disturbances, induced by radio-frequency fields According to:IEC 61326-1
Immunity to conducted, common mode disturbances in the frequency range 0 Hz to 150 kHz According to:IEC 61326-1
Operating conditions
Ambient temperature -10℃~+60℃
Storage temperature -10℃~+60℃
Relative humidity 10%~90%
Environmental requirements The air should not contain any medium corrupting the coat of chrome,nickel and silver.Moreover,violent quiver and impact or any cause of electromagnetic induction (such as big current or spark,etc.)must be avoided when using
Connection data
Conductor cross section AWG min. 12
Conductor cross section AWG max. 24
Screw thread M8
Connection method Screw connection
Others
Cold junction compensation accuracy ±1℃;Effect of compensating conductor resistance≤0.2℃/100Ω
Function
Operation status direction LCD backlight display
说说心中疑问,大家帮您来解答
我要提问
取消
提交
全选
产品大类
分类
名称
语言
下载
1
产品说明书
中文
2
产品说明书
中文
1
2
3
去对比
清空对比栏
询价单 021-64360668
phone
QQ
QQ
电话
询价单
0
顶部
顶部