Product Name | T-24-L Surge protective device |
Nominal operating voltage Un | 24VDC |
Maximun continuous operating voltage Uc | 32VDC |
Nominal Discharge Current In(8/20us) | 10kA |
Certification | TUV SIL3 |
Protected Objects/Systems | AI;AO;DI;DO |
Features | 24V, 20kA; Hot Pluggable; 2 wires |
Protected Objects/Systems | AI; AO; DI; DO |
Depth | 75.0mm |
Height | 90.0mm |
Width | 12.5mm |
Brand | Dinkle |
Material | PA66 |
Protection Level | IP20 |
Flame Retardant Grade | V0 |
Colors | Gray |
Nominal operating voltage Un | 24VDC |
Maximun continuous operating voltage Uc | 32VDC |
Nominal Operating Current IL | 800mA |
Resistance per Wire | 1ohm |
Response Time | 1ns |
Number of Wires | 2 |
Bandwidth | 10MHz(-0.5dB) |
Leakage Current | <1uA |
Nominal Discharge Current In(8/20us) | 10kA |
Maximum Discharge Current Imax(8/20us) | 20kA |
Total Discharge Current Itotal | 40kA |
Impulse Current Iimp(10/350us) | 2.5kA |
Total Impulse Current(10/350us) | 5kA |
Voltage Protection Level Up(8/20us) | 60V(Line to Line)/600V(Line to Ground) |
Voltage Protection Level Up(1kV/us) | 40V(Line to Line)/600V(Line to Ground) |
λSU | 7.26 |
λSD | 0 |
λDU | 2.02 |
λDD | 13.38 |
λtotal | 22.66 |
Safe Failure Fraction(SFF) | 0.9109 |
Safety Integrity Level(SIL) | SIL3 |
Certification | Lightning Protection Certification;Functional Safety Certification |
Explosion-Proof Certification | N/A |
Lightning Protection Certification | Shanghai Lightning Protection Products Test Center |
Functional Safety | SIL3 |
Names | GB/T 18802.21 / IEC 61643-21; IEC 61508 |
Ambient Temperature (Operation) | ﹣40—70℃ |
Ambient Temperature (Storage) | ﹣40—85℃ |
Permissible Humidity (Operation) | 5%—95% |
Applicable Location | Cabinet |
Maximum Altitude | 2000m |
Conductor Cross Section Solid | 0.2—4mm2 |
Conductor Cross Section Flexible | 0.2—2.5mm2 |
Stripping Length | 8mm |
Connection Method | Terminal Connection |
Maximum Tightening Torque | 0.5Nm |
Mounting Position | Cabinet |
Mounting Method | 35mm Lead Rail |
Interface | Screw |