1 input 1 output RTD Input Signal Isolator converter
CZ3071  1 input 1 output RTD Input Signal Isolator converter
RTD 1 input 1 output signal isolator with programmable measuring range for RTD input, 4-20mA output. conversion accuracy is as high as 0.1%, outrange and bolt detection and alarm functions.
Number of channels:
1input/1output
Input signal:
Pt100
Cu50
Cu100
Output signal:
0~20mA
4~20mA;
0~5V
1~5V
Power Supply Mode:
24VDC
Power Connection Mode:
Terminal Power Supply
CZ3071
产品详情
产品参数
下载
click to consult
加入对比
加入询价单

1 input 1 output RTD Input Signal Isolator converter

1 input 1 output RTD Input Signal Isolator converter


Produce Name
 CZ3071 signal isolator converter 
Number of channels
 1 input 1 output
Supply voltage(Ue)  20-35V DC
Input signal  Pt100,Cu50,Cu100
Output signal  0-20mA,4-20mA,0-5V,1-5V
Field apparatus  2-RTD,3-wire RTD

1 input 1 output RTD Input Signal Isolator converter

1 input 1 output RTD Input Signal Isolator converter

Q: What information should I provide before order?

A: Please specify the following information:

1. Which RTD input signal you need? Pt100 or Cu50 or Cu100?

2. Which output signal you need? 4-20mA or 0-20mA or 0/1-5V?

1 input 1 output RTD Input Signal Isolator converter


1 input 1 output RTD Input Signal Isolator converter

Packing information                              


unit packaging size for 1pc of CZ3071 signal isolator:

outer carton for 5 pcs of CZ3071 signal isolator: 17*15*13 cm

outer carton for 10 pcs of CZ3071 signal isolator: 30*18*15 cm

outer carton for 20 pcs of CZ3071 signal isolator: 35*29*14 cm

outer carton for 40 pcs of CZ3071 signal isolator: 35*29*26 cm


FAQ                                                        

Q: What information should I provide before order?

A: Please specify the following information:

1. Which RTD input signal you need? Pt100 or Cu50 or Cu100?

2. Which output signal you need? 4-20mA or 0-20mA or 0/1-5V?

 

Q: How to set the input data?

A: Before order, please confirm the sensor type and range scope you need, we will set as you need before delivery out.

On the other hand, CHENZHU RTD/TC producta are programmable. The configuration software and dedicated adapter will be needed.

 

Q: Are you trading company or manufacturer ?

A: We are manufacturer, providing own brand product and also ODM/OEM services. 

Q: How long is your delivery time?

A: ≤ 20 pcs, generally it is 3~7 working days after 100% down-pay; 20-100 pcs, it is 2~4 weeks after 100% down-pay  according to quantity; More than 100 pcs,  pls contact with our support.

Q: What is your terms of payment ?

A: 100% T/T in advance.


General
Input data
Output data
Power supply
Dimensions
Housing
EMC data
Operating conditions
Connection data
Installation
产品参数
General
Number of channels 1input/1output
Dielectric strength 1500V AC;1minute(among power supply ,input and output )
Temperature drift 0.01%F.S./℃
Response time Reach 90% of final value in 1s
Insulation resistance ≥100MΩ;500V DC(among power supply,input,output and the shell)
Electromagnetic compatibility According to IEC 61326-1(GB/T 18268)
Weight Approx 100g
Field apparatus 2-wire RTD;3-wire RTD
Input data
Input signal Pt100;Cu50;Cu100
Output data
Output signal 0~20mA;4~20mA;0~5V;1~5V
Current output load resistance RL≤300Ω
Voltage output load resistance RL≥20kΩ
Alarm indication Lower than range, LED L falshing, output current ≈3.8mA;Higher than range, LED H falshing, output current ≈20.8mA;Breakage, LED L and H falshing at the same time, output current ≈20.8mA;Short circuit, LED L and H falshing at the same time, output current ≈3mA
Power supply
Supply voltage(Ue) 20~35V DC
Power protection Reverse protection of power supply
Current consumption ≤35mA (at 24Vdc supply,20mA output)
Power supply mode Independent power supply
Power connecting mode Terminal
Dimensions
Depth 114.5mm
Height 99.0mm
Width 17.5mm
Housing
Material PA
Degree of protection IP20
Flammability rating UL94/V0
Colour white
EMC data
Electrical fast transient/burst immunity According to:IEC 61326-1;Class A
Surge immunity According to:IEC 61326-1;Class B
Radiated,radio-frequency,electromagnetic field immunity According to:IEC 61326-1
Electrostatic discharge immunity According to:IEC 61326-1;Class A
Immunity to conducted disturbances, induced by radio-frequency fields According to:IEC 61326-1
Immunity to conducted, common mode disturbances in the frequency range 0 Hz to 150 kHz According to:IEC 61326-1
Operating conditions
Ambient temperature -20℃~+60℃
Storage temperature -40℃~+80℃
Relative humidity 10%~90%
Environmental requirements The air should not contain any medium corrupting the coat of chrome,nickel and silver.Moreover,violent quiver and impact or any cause of electromagnetic induction (such as big current or spark,etc.)must be avoided when using
Connection data
Conductor cross section solid range 0.5~2.5mm²
Conductor cross section flexible range 0.5~2.5mm²
Conductor cross section AWG min. 12
Conductor cross section AWG max. 24
Stripping length 8mm
Screw thread M3
Connection method Screw connection
Tightening torque min. 0.5 Nm
Tightening torque max. 0.6 Nm
Installation
Mounting type DIN35mm
说说心中疑问,大家帮您来解答