Low power SPD (24VDC; In=10kA ) 7073676
T-24  Low power SPD (24VDC; In=10kA ) 7073676
SPD for low power supply; 24VDC; IL:10A; C2: 20kV/10kA, D1: 2.5kA/line; hot-pluggable; grounded through DIN rail
voltage:
24VDC
Nominal discharge current ln:
10kA
contrast
enquire
Generate PDF
T-24
Product details
Download
Product Features
Protections
Dimensions
Housing
Basic Parameter
Security Data(Lightning Protection)
Product Approvals
Certification
Standards
Ambient Requirements
Connection Parameters
Mounting

Low power SPD (24VDC; In=10kA ) 7073676

Low power SPD (24VDC; In=10kA ) 7073676



Product Name  T-24 Surge protective device
Nominal operating voltage Un  24VDC
Maximun continuous operating voltage Uc  36VDC
Nominal Discharge Current In(8/20us)  10kA
Features  20kA;Hot Pluggable;24V DC
Protected Objects/Systems  24VDC




Low power SPD (24VDC; In=10kA ) 7073676

Low power SPD (24VDC; In=10kA ) 7073676

Low power SPD (24VDC; In=10kA ) 7073676

Low power SPD (24VDC; In=10kA ) 7073676

Low power SPD (24VDC; In=10kA ) 7073676


Technichal Data
Product Features
Features 20kA; Hot Pluggable; 24V DC
Protections
Protected Objects/Systems 24VDC
Dimensions
Depth 75.0mm
Height 90.0mm
Width 12.5mm
Housing
Brand Dinkle
Material PA66
Protection Level IP20
Flame Retardant Grade V0
Colors Gray
Basic Parameter
Nominal operating voltage Un 24VDC
Maximun continuous operating voltage Uc 36VDC
Nominal Operating Current IL 16A
Response Time 1ns
Number of Wires 2
Leakage Current <1uA
Security Data(Lightning Protection)
Nominal Discharge Current In(8/20us) 10kA
Maximum Discharge Current Imax(8/20us) 20kA
Total Discharge Current Itotal 40kA
Impulse Current Iimp(10/350us) 2.5kA
Total Impulse Current(10/350us) 5kA
Voltage Protection Level Up(8/20us) 85V(Line to Line)/600V(Line to Ground)
Product Approvals
Certification Lightning Protection Certification
Certification
Explosion-Proof Certification N/A
Lightning Protection Certification Shanghai Lightning Protection Products Test Center
Standards
Names GB/T 18802.21 / IEC 61643-21; IEC 61508
Ambient Requirements
Ambient Temperature (Operation) ﹣40—70℃
Ambient Temperature (Storage) ﹣40—85℃
Permissible Humidity (Operation) 10%—90%
Applicable Location Cabinet
Maximum Altitude 2000m
Connection Parameters
Conductor Cross Section Solid 0.2—4mm2
Conductor Cross Section Flexible 0.2—2.5mm2
Stripping Length 8mm
Connection Method Terminal Connection
Maximum Tightening Torque 0.5Nm
Mounting
Mounting Position Cabinet
Mounting Method 35mm Lead Rail
Interface Screw
"Hey, let's talk about your concerns~"
I Want To Ask Questions
Cancel
Submit
Select All
No.
Type
Name/Description
Language
Download
1
Manual
English
1
2
3
go contrast
empty contrast
Enquire
Enquire
Tel
Tel
021-64360668
My Enquiry
My Enquiry
0
Comparison
Comparison
0
Top
Top